Contractors & trades / Electrical Load Calculator

Electrical Load Calculator

Add up the watts on a circuit or small panel to get total amps and check them against the breaker with the 80% rule for continuous loads. This is an estimate only: verify against NEC Article 220 and local code, and have a licensed electrician confirm.
Lights

Enter a number from 0 to 100000

Whole number, 0–1000

Computers

Enter a number from 0 to 100000

Whole number, 0–1000

Appliance

Enter a number from 0 to 100000

Whole number, 0–1000

Heater or AC

Enter a number from 0 to 100000

Whole number, 0–1000

Motor or tool

Enter a number from 0 to 100000

Whole number, 0–1000

Other

Enter a number from 0 to 100000

Whole number, 0–1000

Enter a number from 1 to 4000

Continuous loads should stay at or under 80% of the breaker rating, so a 20 A breaker carries 16 A.

Total current
14.17 A
1,700 Wtotal load
88.5%of 80% breaker limit
20 Asmallest standard breaker
Lights · 1 × 300 W300 W
Computers · 2 × 250 W500 W
Appliance · 1 × 900 W900 W
Total watts1,700 W
Amps at 120 V · watts ÷ volts14.17 A
Usable on a 20 A breaker · 80% for continuous loads16 A
Room left · 220 W1.83 A

Uses nameplate watts at unity power factor. This is an estimate; NEC Article 220 load calculations, local code and a licensed electrician govern panel and service sizing.

See breakdown

How the electrical load calculation works

  1. Add up the watts

    Use the nameplate wattage of each device times how many you have. 300 W of lights, two 250 W computers and a 900 W coffee maker total 1,700 W.

  2. Amps = watts ÷ volts

    1,700 W on a 120 V circuit draws 14.17 A. On 240 V the same load draws half that. For three-phase, divide by 1.732 × volts.

  3. Hold continuous loads to 80% of the breaker

    A load that runs three hours or more should not exceed 80% of the breaker rating. A 20 A breaker carries 16 A continuous; a 15 A breaker carries 12 A.

  4. Smallest breaker = amps ÷ 0.8, rounded up

    14.17 A ÷ 0.8 = 17.7 A, so the next standard size is 20 A. The wire must be rated for that breaker too.

Worked example. Lights at 300 W, two 250 W computers and a 900 W coffee maker total 1,700 W. At 120 V that is 14.17 A. A 20 A breaker allows 16 A for continuous use, so the circuit is at 88.5% of its limit with 1.83 A (220 W) to spare.

Electrical Load FAQ

How do I calculate the electrical load on a circuit?

Add the watts of everything that runs at the same time and divide by the circuit voltage. 1,800 W on 120 V is 15 A.

What is the 80% rule for breakers?

A continuous load, one that runs three hours or more, should use no more than 80% of the breaker's rating. That is 12 A on a 15 A breaker and 16 A on a 20 A breaker.

How many watts can a 20 amp circuit handle?

2,400 W at 120 V in theory, and 1,920 W for a continuous load under the 80% rule. On 240 V the figures double.

How many watts can a 15 amp circuit handle?

1,800 W at 120 V in theory, and 1,440 W for a continuous load under the 80% rule. A heater with a 1,500 W nameplate draws 12.5 A at 120 V, which is already over the 12 A continuous limit.

What size breaker do I need for a load?

Divide the amps by 0.8 for a continuous load and round up to the next standard breaker size. 6,200 W on 240 V is 25.83 A, and 25.83 ÷ 0.8 = 32.3 A, so the calculator shows 35 A. The wire must be rated for that breaker, and a licensed electrician should confirm the size against the NEC and local code.

How do I calculate the load for an electrical panel?

A full panel or service load uses NEC Article 220, which applies demand factors to lighting, appliances, heating and cooling. This tool adds connected loads only, so it overstates a real service load; have an electrician do the Article 220 calculation.

Can I put a bigger breaker on an overloaded circuit?

No. The breaker protects the wire. Upsizing it without upsizing the wire is a fire risk; split the load across circuits instead, and have a licensed electrician check the circuit.

Sources: NFPA 70, National Electrical Code 2023 (free read-only access)

Related calculators